Want your own numbers?
The industrial chiller operating cost calculator takes your tons, load, kW/ton, hours and electricity rate and compares your chiller against an older or less efficient baseline.
1. What kW per ton means
kW/ton is the electrical power a chiller draws for each ton of cooling it delivers. One ton of refrigeration is 12,000 Btu/h, the heat needed to melt one short ton of ice in 24 hours.
Unlike COP and EER, lower kW/ton is better. A chiller at 0.55 kW/ton uses about 39% less electricity than one at 0.90 kW/ton for the same cooling.
2. Converting kW/ton to COP and EER
3.517 is the number of kilowatts in one ton of refrigeration. Common values:
| kW/ton | COP | EER |
|---|---|---|
| 0.50 | 7.03 | 24.0 |
| 0.60 | 5.86 | 20.0 |
| 0.70 | 5.02 | 17.1 |
| 0.80 | 4.40 | 15.0 |
| 1.00 | 3.52 | 12.0 |
| 1.20 | 2.93 | 10.0 |
3. How to measure kW/ton on a running chiller
You need three measurements taken at the same time:
- Chilled water flow in gpm, from a flow meter or the pump curve and differential pressure.
- Chilled water ΔT: return temperature minus supply temperature, in °F.
- Chiller input power in kW, from the chiller panel or a power meter on the feeder.
The 24 comes from 500 × gpm × ΔT ÷ 12,000. Example: a chiller cooling 720 gpm from 54°F to 44°F delivers 720 × 10 ÷ 24 = 300 tons. If it draws 195 kW, it is running at 195 ÷ 300 = 0.65 kW/ton.
Small sensor errors matter. At a 10°F ΔT, a 0.5°F error in one temperature sensor moves the tonnage, and so the kW/ton, by about 5%. Calibrate or check the sensors against each other before trusting a trend.
For glycol loops, the constant changes because glycol carries less heat per gallon than water. The glycol chiller derating guide explains the correction.
4. Full load vs part load: IPLV and NPLV
Chillers spend most of the year below full load, and many are more efficient at part load. AHRI Standard 550/590 defines a single weighted figure, the Integrated Part Load Value (IPLV), from efficiency at 100%, 75%, 50% and 25% load. When kW/ton is used, the weighting is applied to the reciprocals:
Here A, B, C and D are the kW/ton at 100%, 75%, 50% and 25% load. A chiller rated 0.58, 0.50, 0.42 and 0.45 kW/ton at those points has an IPLV of about 0.456 kW/ton, far better than its full-load rating suggests. NPLV is the same calculation at your own design conditions rather than AHRI standard conditions.
IPLV is a comparison tool, not a forecast. Its weights describe a typical building-style load profile. A process chiller that runs near full load around the clock should be judged mostly on its full-load kW/ton.
5. Typical kW/ton by chiller type
- Water-cooled centrifugal: commonly around 0.5 to 0.6 kW/ton at full load. Variable-speed and magnetic-bearing machines can be much lower at part load.
- Water-cooled screw: commonly around 0.6 to 0.75 kW/ton at full load.
- Air-cooled screw or scroll: commonly around 1.0 to 1.3 kW/ton including condenser fans, because rejecting heat to dry air needs a higher condensing temperature.
These are broad ranges, not minimum standards. For code minimums, check the edition of ASHRAE 90.1 or the energy code your jurisdiction has adopted. The air-cooled vs water-cooled chiller comparison covers the trade-offs, including the water and cooling tower costs that come with water-cooled plants.
6. What a better kW/ton is worth
Take a plant with an average load of 300 tons for 4,000 hours a year at $0.12/kWh:
| Chiller | kW/ton | kWh per year | Cost per year |
|---|---|---|---|
| Older chiller | 0.90 | 1,080,000 | $129,600 |
| Modern chiller | 0.60 | 720,000 | $86,400 |
| Difference | 0.30 | 360,000 | $43,200 |
Each 0.01 kW/ton is worth about $1,440 a year in this example. That is why a chiller with a higher price and a better kW/ton often has the lower total cost of ownership. The chiller ROI and energy savings guide shows how to work out the payback.
7. Why kW/ton creeps up, and how to bring it down
- Condenser tube fouling: scale and biofilm raise the condensing temperature. A rising condenser approach temperature (condensing temperature minus leaving condenser water temperature) is the usual warning sign. Good water treatment and the right cooling tower cycles of concentration keep tubes clean.
- Chilled water setpoint: running colder than the process needs makes the compressor work harder. A common rule of thumb is roughly 1% to 2% of chiller energy for each °F, so raise the setpoint where the process allows.
- Condenser water temperature: cooler condenser water lowers kW/ton, within the chiller manufacturer's minimum limits. Tower fan control and condenser water reset strategies use this.
- Low load on a big chiller: a chiller that is far too large for the load cycles or runs at its least efficient point. See chiller sizing mistakes.
- Refrigerant charge and non-condensables: both a low charge and air in the condenser raise power. Your service contractor checks these during the annual inspection.
Frequently asked questions
What is a good kW per ton for a chiller?
Lower is better. Modern water-cooled centrifugal chillers often run around 0.5 to 0.6 kW/ton at full load and lower at part load. Air-cooled chillers are commonly around 1.0 to 1.3 kW/ton including condenser fans. Compare chillers at the same rating conditions, using the manufacturer's AHRI-certified data.
How do you convert kW/ton to COP?
COP = 3.517 ÷ kW/ton. A chiller at 0.6 kW/ton has a COP of about 5.86. To convert to EER, use EER = 12 ÷ kW/ton, so 0.6 kW/ton is an EER of 20.
How do you calculate chiller tons from flow and temperature?
For water, tons = gpm × ΔT (°F) ÷ 24. A chiller cooling 720 gpm from 54°F to 44°F is delivering 300 tons. For glycol mixtures, correct for the lower specific heat and higher density of the fluid.
What is the difference between kW/ton and IPLV?
kW/ton is the efficiency at one operating point, usually full load. IPLV (or NPLV at non-standard conditions) is a weighted average across 100%, 75%, 50% and 25% load defined in AHRI Standard 550/590. Most chillers spend most of their hours at part load, so IPLV is usually the better guide to annual energy.
Does kW/ton include pumps and the cooling tower?
A chiller nameplate kW/ton covers the chiller only. A whole-plant kW/ton adds chilled water pumps, condenser water pumps and cooling tower fans, so it is always higher. Be clear which one you are comparing.
Sources and further reading
- AHRI Standard 550/590: Performance Rating of Water-Chilling and Heat Pump Water-Heating Packages
- ASHRAE Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings (chiller efficiency tables)
- U.S. Department of Energy, Federal Energy Management Program: chiller and chilled water plant guidance
Put a price on your chiller's efficiency
Enter your tons, load, kW/ton and electricity rate to see annual energy, cost per ton-hour and savings against an older chiller.