Chiller kW per Ton Explained

kW/ton is the number that decides most of a chiller's lifetime cost. This guide shows how to calculate it, how it relates to COP, EER and IPLV, and how to turn a difference of a few hundredths into dollars.

Published: October 13, 2026•By AMCalculator Editorial Team

Want your own numbers?

The industrial chiller operating cost calculator takes your tons, load, kW/ton, hours and electricity rate and compares your chiller against an older or less efficient baseline.

1. What kW per ton means

kW/ton is the electrical power a chiller draws for each ton of cooling it delivers. One ton of refrigeration is 12,000 Btu/h, the heat needed to melt one short ton of ice in 24 hours.

kW/ton = input power (kW) ÷ cooling delivered (tons)

Unlike COP and EER, lower kW/ton is better. A chiller at 0.55 kW/ton uses about 39% less electricity than one at 0.90 kW/ton for the same cooling.

2. Converting kW/ton to COP and EER

COP = 3.517 ÷ kW/ton
EER (Btu/Wh) = 12 ÷ kW/ton

3.517 is the number of kilowatts in one ton of refrigeration. Common values:

kW/tonCOPEER
0.507.0324.0
0.605.8620.0
0.705.0217.1
0.804.4015.0
1.003.5212.0
1.202.9310.0

3. How to measure kW/ton on a running chiller

You need three measurements taken at the same time:

  1. Chilled water flow in gpm, from a flow meter or the pump curve and differential pressure.
  2. Chilled water ΔT: return temperature minus supply temperature, in °F.
  3. Chiller input power in kW, from the chiller panel or a power meter on the feeder.
Tons (water) = gpm × ΔT (°F) ÷ 24

The 24 comes from 500 × gpm × ΔT ÷ 12,000. Example: a chiller cooling 720 gpm from 54°F to 44°F delivers 720 × 10 ÷ 24 = 300 tons. If it draws 195 kW, it is running at 195 ÷ 300 = 0.65 kW/ton.

Small sensor errors matter. At a 10°F ΔT, a 0.5°F error in one temperature sensor moves the tonnage, and so the kW/ton, by about 5%. Calibrate or check the sensors against each other before trusting a trend.

For glycol loops, the constant changes because glycol carries less heat per gallon than water. The glycol chiller derating guide explains the correction.

4. Full load vs part load: IPLV and NPLV

Chillers spend most of the year below full load, and many are more efficient at part load. AHRI Standard 550/590 defines a single weighted figure, the Integrated Part Load Value (IPLV), from efficiency at 100%, 75%, 50% and 25% load. When kW/ton is used, the weighting is applied to the reciprocals:

IPLV (kW/ton) = 1 ÷ (0.01/A + 0.42/B + 0.45/C + 0.12/D)

Here A, B, C and D are the kW/ton at 100%, 75%, 50% and 25% load. A chiller rated 0.58, 0.50, 0.42 and 0.45 kW/ton at those points has an IPLV of about 0.456 kW/ton, far better than its full-load rating suggests. NPLV is the same calculation at your own design conditions rather than AHRI standard conditions.

IPLV is a comparison tool, not a forecast. Its weights describe a typical building-style load profile. A process chiller that runs near full load around the clock should be judged mostly on its full-load kW/ton.

5. Typical kW/ton by chiller type

  • Water-cooled centrifugal: commonly around 0.5 to 0.6 kW/ton at full load. Variable-speed and magnetic-bearing machines can be much lower at part load.
  • Water-cooled screw: commonly around 0.6 to 0.75 kW/ton at full load.
  • Air-cooled screw or scroll: commonly around 1.0 to 1.3 kW/ton including condenser fans, because rejecting heat to dry air needs a higher condensing temperature.

These are broad ranges, not minimum standards. For code minimums, check the edition of ASHRAE 90.1 or the energy code your jurisdiction has adopted. The air-cooled vs water-cooled chiller comparison covers the trade-offs, including the water and cooling tower costs that come with water-cooled plants.

6. What a better kW/ton is worth

Annual cost = kW/ton × average tons × hours × $/kWh

Take a plant with an average load of 300 tons for 4,000 hours a year at $0.12/kWh:

ChillerkW/tonkWh per yearCost per year
Older chiller0.901,080,000$129,600
Modern chiller0.60720,000$86,400
Difference0.30360,000$43,200

Each 0.01 kW/ton is worth about $1,440 a year in this example. That is why a chiller with a higher price and a better kW/ton often has the lower total cost of ownership. The chiller ROI and energy savings guide shows how to work out the payback.

7. Why kW/ton creeps up, and how to bring it down

  • Condenser tube fouling: scale and biofilm raise the condensing temperature. A rising condenser approach temperature (condensing temperature minus leaving condenser water temperature) is the usual warning sign. Good water treatment and the right cooling tower cycles of concentration keep tubes clean.
  • Chilled water setpoint: running colder than the process needs makes the compressor work harder. A common rule of thumb is roughly 1% to 2% of chiller energy for each °F, so raise the setpoint where the process allows.
  • Condenser water temperature: cooler condenser water lowers kW/ton, within the chiller manufacturer's minimum limits. Tower fan control and condenser water reset strategies use this.
  • Low load on a big chiller: a chiller that is far too large for the load cycles or runs at its least efficient point. See chiller sizing mistakes.
  • Refrigerant charge and non-condensables: both a low charge and air in the condenser raise power. Your service contractor checks these during the annual inspection.

Frequently asked questions

What is a good kW per ton for a chiller?

Lower is better. Modern water-cooled centrifugal chillers often run around 0.5 to 0.6 kW/ton at full load and lower at part load. Air-cooled chillers are commonly around 1.0 to 1.3 kW/ton including condenser fans. Compare chillers at the same rating conditions, using the manufacturer's AHRI-certified data.

How do you convert kW/ton to COP?

COP = 3.517 ÷ kW/ton. A chiller at 0.6 kW/ton has a COP of about 5.86. To convert to EER, use EER = 12 ÷ kW/ton, so 0.6 kW/ton is an EER of 20.

How do you calculate chiller tons from flow and temperature?

For water, tons = gpm × ΔT (°F) ÷ 24. A chiller cooling 720 gpm from 54°F to 44°F is delivering 300 tons. For glycol mixtures, correct for the lower specific heat and higher density of the fluid.

What is the difference between kW/ton and IPLV?

kW/ton is the efficiency at one operating point, usually full load. IPLV (or NPLV at non-standard conditions) is a weighted average across 100%, 75%, 50% and 25% load defined in AHRI Standard 550/590. Most chillers spend most of their hours at part load, so IPLV is usually the better guide to annual energy.

Does kW/ton include pumps and the cooling tower?

A chiller nameplate kW/ton covers the chiller only. A whole-plant kW/ton adds chilled water pumps, condenser water pumps and cooling tower fans, so it is always higher. Be clear which one you are comparing.

Sources and further reading

  • AHRI Standard 550/590: Performance Rating of Water-Chilling and Heat Pump Water-Heating Packages
  • ASHRAE Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings (chiller efficiency tables)
  • U.S. Department of Energy, Federal Energy Management Program: chiller and chilled water plant guidance